Rail mounting device, 4 rail units
ETS product family: Physical sensors
Product type: Energy detector
The energy detector has three channels for connecting loads to up to three separate phases with a common neutral conductor. Each channel can measure:
- Voltage (eff.)
- Current (eff.)
- Active power
- Reactive power
Additionally, the active power and reactive power of all channels will be summed up and displayed as three-phase power values along with the mains frequency. According to the parameterisation the measured values will be transmitted on the KNX bus, either cyclically and / or when the value changes. An additional telegram will be transmitted if certain values exceed or fall below a specified limit.
The following meters exist for each channel and for the three-phase values:
- 1 x energy meter total
- 1 x energy meter ¼ h value
- 3 x energy meter n
- 3 x energy intermediate meter n
- Direct measurement (without transformer)
- Transformer measurement (with external 75 A transformer, ratio 75:5, e.g. Phoenix Contact order key 2277611)
Power supply via E1/N | |
Rated voltage: | AC 110 ... 240 V ~ |
Mains frequency: | 50/60 Hz |
Power consumption: | max. 2 W |
Inputs E1 ... E3 | |
Rated voltage range: | AC 110 ... 240 V ~ |
Rated current range: | 4 mA ... 16 A |
Rated frequency: | 50/60 Hz |
Measurands: | voltage (rms value) current (rms value) frequency active power (signed +/-) reactive power (signed +/-) active energy (signed +/-) |
External transformer | |
Transformation ratio: | 75:5 |
Secondary current: | 0 ... 5 A |
Accuracy: | |
Direct measurement (without transformer): | 1 % of 200 mA ... 16 A |
Transformer measurement (75 A transformer, class 1): | 2 % of 7.5 A ... 75 A |
Pulses LED: | |
Direct measurement (without transformer): | 6400 / kWh |
Transformer measurement (75 A transformer): | 427 / kWh |
Pulse duration: | 4.9 ms |
Power loss | |
Voltage measurement: | ≤ 0.03 W / phase |
Current measurement: | ≤ 0.8 W / phase |
Power consumption from mains: | < 1 W |
Connection | |
Connection mode: | screw terminals |
single wire: | 0.5 ... 2.5 mm² |
stranded without ferrule: | 0.5 ... 2.5 mm² |
stranded with ferrule: | 0.5 ... 2.5 mm² |
Ambient temperature: | -5 ... +45 °C |
Storage/transport temperature: | -25 ... +70 °C |
Mounting width: | 72 mm (4 rail units) |
KNX medium: | TP 256 |
Rated voltage KNX: | DC 21 ... 32 V SELV |
Current consumption KNX: | typical 10 mA |
Connection, KNX: | terminal |