null
  Loading... Please wait...

Categories

KNX Binary Input 8-G - 2128 REG

Hover over image to zoom

  • Image 1
Jung
PLN1,221.08 (inc VAT) PLN1,017.58 (exc VAT)
SKU:
2128REG
Weight:
0.22 KGS
Availability:
5 - 10 days lead time

 Product Description

Rail mounting device, 4 rail units
8 inputs 12 ... 48 V AC/DC
Auxiliary voltage output DC 24 V (SELV) for polling potential-free contacts
with status indicator
ETS product family: Input
Product type: Binary input

Intended Use

- Polling of conventional switching or push-button contacts, glass break detectors etc. in KNX systems, for reporting of states, operation of loads, etc.
- Mounting on DIN rail according to EN 60715 in distribution boxes

Characteristics

- Status LED for each input
- Detection of voltage levels and changes on the input
- Transmitting the input state to the bus
- Transmission behaviour freely settable
- Functions: switching, dimming, blinds up/down, brightness values, temperatures, calling up and saving scenes
- Inputs can be disabled separately
- External AC and DC voltages can be connected
- Auxiliary voltage output for polling potential-free contacts
- No separate power supply required
- Separate reference potentials for inputs
- Pulse counter (firmware version V02 or higher), also suitable for S0 pulses

Technical Details

Rated voltage KNX: DC 21 ... 32 V SELV
Power consumption KNX: max. 350 mW
Stand-by: max. 200 mW
Connection, KNX: terminal
Ambient temperature: -5 ... +45 °C
Storage/transport temperature: -25 ... +70 °C
Inputs
Rated voltage: AC/DC 12 ... 48 V
Signal level "0" signal: AC/DC -48 ... +2 V
Signal level "1" signal: AC/DC 8 ... 48 V
Input current at rated voltage
Input current: approx. 2 mA
Signal duration: min. 30 ms
Rated frequency AC signal: 30 ... 60 Hz
Number of contacts per input
NO contacts: unlimited
NC contacts: max. 20
Output voltage: DC 24 V SELV
Mounting width: 72 mm (4 rail units)
Stand-by power: max. 200 mW
Power loss: max. 1 W
Connection
Connection mode: screw terminals
single wire: 0.2 ... 4 mm²
stranded without ferrule: 0.34 ... 4 mm²
stranded with ferrule: 0.14 ... 2.5 mm²
Cable length: max. 100 m

 

Downloads

Operating Instruction
Manual
ETS File

 Find Similar Products by Category

 Product Reviews

This product hasn't received any reviews yet. Be the first to review this product!

You Recently Viewed...

 

What's News

newsletter

I would like to receive occasional newsletters regarding new products and promotions.

Follow us on

Copyright 2024 Home of Technologies Limited. All Rights Reserved.
 Sitemap | Our Privacy Policy | Store devoleped and designed by Home of Technologies marketing department

Click the button below to add the KNX Binary Input 8-G - 2128 REG to your wish list.