Loading... Please wait...Currency Displayed in
Enables humidity control devices to be switched on according to needs
- Monitoring and regulation of relative air humidity in rooms by controlling fans, drying units and air humidifiers
- Variable relative humidity as setpoint based on printed scale in % rh
- Measurement taken via a measuring element of stabilised synthetic textile tape.
- Micro-switch with fixed switching difference XSd
| Power Supply | |
| Max. load | 5(3) A, 250 V~ |
| Min. load | 100 mA, 24 V |
| Parameters | |
| Setting range | 30...90% rh |
| Setting accuracy | ±5% rh |
| Humidity calibration at | 55% rh, 23 °C |
| Switching difference | Typ. 6% rh |
| Long-term stability | Approx. -1.5% rh/a |
| Time constant in moving air (0.2 m/s) | Approx. 5 min |
| Temperature influence | 0.5% rh/K |
| Type | Nominal Diameter |
| HSC120F001 | External setpoint adjuster |
| HSC120F010 | Internal setpoint adjuster |