Enables controlling of HVAC components according to needs.
- Room temperature can be set as the setpoint using the printed temperature scale
- Variants of the standard devices are available, such as thermal feedback, night set-back mode, fan switches and switches for heating/cooling
- Setpoint adjuster with mechanical min. and max. limitation of the setting range
Power Supply | |
load | 230 V~ 10(2,5) A, 24 V= max. 1 A, 24 V~ min. 0.2 A |
Parameters | |
Setting range | 5...30 °C |
Night-time reduction (N/R) | Approx. 5 K |
Time constant in still air | 17 min |
Time constant in moving air (0.2 m/s) | 13 min |
Thermal feedback - Proportional band | Approx. 3 K |
Thermal feedback - Shortest switching interval | Approx. 19 min (E = 0.5) |
Power supply: 10% more voltage means P-band approx. 4 K, switching period = 15 min, actualvalue reduction = approx. 0.5 K | |||
H/C = heating or cooling, depending on connection; H//C = heating or cooling, selectable | |||
Type | Operating Mode Switch | Output For | Power Supply |
TSO670F001 | - | H/C | - |
TSO672F001 | Heating/OFF/Cooling | H//C | - |
TSH670F002 | - | H/C | 230 V~, ±10%, 50...60 Hz |
TSH676F002 | - | H/C | 230 V~, ±10%, 50...60 Hz |