Currency Displayed in
The KNX-Sensor SK10-TC-ATF2 is used for measuring and controlling indoor air temperature in indoor / outdoor and damp locations (IP54/65) with external sensor (PT1000 in a 30mm protective tube made of V4A steel Ø 6 mm) on the front side of the plastic housing.
The housing is suitable for wall mounting and is mounted with 2 screws.
- Air temperature ( sensor on housing ) also weighted with external temperature
- Control functions for heating and cooling applications ( can be combined )
- Setpoint temperatures for Comfort, Standby, Economy and Protection, selectable via KNX HVAC objects
- Setpoint change via objects
- Storage of minimum- and maximum-temperature
- Heat- and frost-alarm
- Limits for temperature
- Fan control by external inputs
- Adaptation for setpoint and maximum temperatures
- Controller output 0…100% or programmable PWM for thermal actuators
- Valve rinse function
- Second temperature controller as auxiliary controller
Four logic blocks for the logical link between internal and external signals
- 10 associated logic inputs / outputs
- Heat- and cooling-request as additionally available signals
- Functions "AND, OR, NOT, XOR" for binary logic
- Functions "+ - *" for 8-bit values
- Function "=" for conditional forwarding of events
Measurement: | Temperature |
Control: | Integrated |
Temperature Range: | -50 .. +90°C |
Resolution: | ± 0,01°C |
Accuracy: | ± 0,3°C + accuracy of the sensor |
Operating Voltage: | KNX Bus Voltage 21 .. 32VDC |
Power Consumption: | approx. 240mW ( at 24VDC ) |
Environment Temperature KNX-Module: | Storage: -25 .. +85°C Operating: -25 .. +80°C |
Environment Humidity KNX-Module: | 0 .. 95% r.H Non Condensing |
Bus Coupler: | Integrated |
Auxiliary Supply: | Not Required |
Startup with the ETS Version 4 or higher: | HLK305 |
Curcuit Points: | KNX 2-Pole Clamps ( red / black ) |
Protection Class: | IP54/65 |
Housing KNX-Module: | Plastic |
Dimensions Housing KNX-Module: | ( 72 x 64 x 40 ) mm |
Article Number: | 30511007 |