- Occupancy detector with circular detection area
- One channel for light switching
- One additional potential-free (dry) contact for HVAC
- Version as master device
- Extension of the detection area with slave devices possible
- Manual switching via push-button possible
- Alarm pulse: the detector triggers only when three movements are detected within 9 seconds
- Additional functions can be set up using the optional remote control.
- Factory settings 10 min and 500 lux (15 min HVAC)
- Zero crossing switching
| Voltage: | 110 - 240 V AC 50 / 60 Hz |
| Dimensions: | SM= Ø 98 x 47 mm FM= Ø 98 x 65 mm FC= Ø 80 x 85 mm |
| Power consumption: | approx. 0.5 W |
| Detection area: | vertical 360° |
| Range: | max. Ø 10 m across max. Ø 6 m towards max. Ø 4 m seated |
| Monitored area (tangential movement): | 79 m² / 2.5 m mounting height |
| Mounting height min./max./recommended: | 2 m / 5 m / 2.5 m |
| Degree / class of protection: | IP20 / Class II |
| Ambient temperature: | -25 °C to +50 °C |
| Housing: | Polycarbonate, UV-resistant |
| Channel 1 (lighting control) | |
| Switching power: | 2300 W, cos φ = 1 |
| 1150 VA, cos φ = 0.5 | |
| 300 W LED | |
| max. inrush current Ip (20 ms) = 165 A | |
| max. inrush current Ip (200 µs) = 800 A | |
| Type of contact: | 1x µ-contact, NO contact with tungsten pre-make contact |
| Follow-up time: | 15 sec - 30 min, Pulse |
| Switch-on threshold: | 10 - 2000 Lux |
| Channel 2 (HVAC control potential-free (dry)) | |
| Switching power: | 3 A / 230 V, cos φ = 1 |
| Type of contact: | 1x µ-contact, dry NO contact |
| Follow-up time: | 5 min - 120 min, Alarm pulse, Pulse |
| Mixed light measuring | |
- IR-Adapter for Smartphones - 92726
- IR-PD-2C - 92475
- IR-PD-Mini - 92159
- Wire basket BSK (Ø 200 x 90 mm) - 92199
- RC-Arc extinction kit - 10880
- Mini-RC-Arc extinction kit - 10882
- SM socket IP54 PD2/PD4-SM - 92161