null
  Loading... Please wait...

Categories

KNX Switch Actuator 8-G C-Load with Current Detection AC 110-230V - 2308.16 REGCHM

Hover over image to zoom

  • Image 1
Jung
¥74,353.74 (inc VAT) ¥61,960.82 (exc VAT)
SKU:
2308.16REGCHM
Weight:
0.65 KGS
Availability:
5 - 10 days lead time

 Product Description

Rail mounting device, 8 rail units
8 NO contacts with manual mechanical operation and status indicator
Only with the ETS 3.0d version or later versions the full functionality will be available.
ETS product family: Output
Product type: Binary output

Intended Use

- Switching of 110 ... 230 V AC or 24 V AC/DC electrical loads with floating contacts
- Mounting on DIN rail according to EN 60715 in distribution boxes

Characteristics

- Manual switching of the relays is independent of the bus
- Operation as NO or NC contacts
- Logic operation and forcing function
- Switching feedback (bus operation only)
- Switch position display
- Central switching function with collective feedback
- Disabling function for each channel
- Time functions: switch-on delay, switch-off delay, staircase lighting timer with pre-warning function
- Integration into light scenes
- Operating hours counter, configurable via bus
- Input monitoring for cyclical updating with safety circuit
- No additional power supply necessary
- Current detection: measurement of the load current for each output
- Monitoring of threshold values for load monitoring, e.g. for reporting load drop-out
- Switching of capacitive loads and the resulting high switch-on currents

Technical Details

Rated voltage KNX: DC 21 ... 32 V SELV
Connection, KNX: terminal
Power consumption KNX: typical 240 mW
Power loss: max. 8 W
Ambient temperature: -5 ... +45 °C
Storage/transport temperature: -25 ... +70 °C
Mounting width: 144 mm (8 rail units)
Connection, outputs
Connection mode: screw terminals
single wire: 0.5 ... 4 mm²
stranded without ferrule: 0.5 ... 4 mm²
stranded with ferrule: 0.5 ... 2.5 mm²
Current detection (sine)
Mains frequency: 50/60 Hz
Measuring range: 0.25 ... 16 A
Accuracy (≤ 1 A): ±100 mA
Accuracy (> 1 A): ±8 % of curr. val.
Switching outputs
Contact type: floating relay contacts (μ contact)
Switching voltage AC: AC 250 / 400 V
Switching current 230 V AC1: 16 A
Switching current 230 V AC3: 10 A
Switching current 400 V AC1: 10 A
Switching current 400 V AC3: 6 A
Fluorescent lamps: 16 AX
Ohmic load: 3680 W
Capacitive load: 16 A / 200 µF
Switching voltage DC: DC 12 ... 24 V
Switching current DC: 16 A
Min. switching current: 100 mA
Switch-on current 150 µs: 600 A
Switch-on current 600 µs: 300 A
Lamp loads
Incandescent lamps: 3680 W
HV halogen lamps: 3680 W
LV halogen lamps with
inductive transformers: 2000 VA
electronic transformers: 2500 W
Fluorescent lamps T5/T8
non-compensated: 3680 W
parallel compensated: 2500 W / 200 µF
lead-lag circuit: 3680 W / 200 µF
Compact fluorescent lamps
non-compensated: 3680 W
parallel compensated: 2500 W / 200 µF
Mercury vapour lamps
non-compensated: 3680 W
parallel compensated: 3680 W / 200 µF
Approvals: VDE

 

Downloads

Operating Instruction
Manual
ETS File

 Find Similar Products by Category

 Product Reviews

This product hasn't received any reviews yet. Be the first to review this product!

You Recently Viewed...

 

What's News

newsletter

I would like to receive occasional newsletters regarding new products and promotions.

Follow us on

Copyright 2024 Home of Technologies Limited. All Rights Reserved.
 Sitemap | Our Privacy Policy | Store devoleped and designed by Home of Technologies marketing department

Click the button below to add the KNX Switch Actuator 8-G C-Load with Current Detection AC 110-230V - 2308.16 REGCHM to your wish list.