Currency Displayed in
Rail mounting device, 8 rail units
Switch actuator: max. 16-gang
Blind actuator: max. 8-gang
Max. 6-gang switch actuator/5-gang blind actuator in combination
with manual electronic operation and LED status indication
Only with the ETS 3.0d version or later versions the full functionality will be available.
ETS product family: Output
Product type: Binary output
- Switching of AC 110 ... 230 V electrical loads with floating contacts
- Switching of electrically-driven blinds, shutters, awnings and similar hangings
- Mounting on DIN rail in small distributors
- Outputs can be operated manually, construction site mode
- Feedback in manual mode and in bus mode
- Scene function
- Disabling of individual outputs manually or by bus
- Operation as NO or NC contacts
- Logic operation and forcing function
- Feedback function
- Central switching function with collective feedback
- Time functions: switch-on delay, switch-off delay, staircase lighting timer with pre-warning function
- Suitable for 110 ... 230 V AC motors
- Blind/shutter position directly controllable
- Slat position directly controllable
- Feedback of movement status, blind/shutter position and slat position
- Forced position through higher-level controller
- Safety function: 3 independent wind alarms, rain alarm, frost alarm
- Sun protection function
The total current of two adjacent outputs must not exceed 20 A.
Power supply | |
Rated voltage: | AC 230/240 V ~ |
Mains frequency: | 50/60 Hz |
Power loss: | max. 4.5 W |
Ambient temperature: | -15 ... +45 °C |
Storage/transport temperature: | -25 ... +70 °C |
Outputs | |
Contact type: | floating relay contacts (μ contact) |
Switch type: | NO contact |
Switching voltage: | AC 250 V ~ |
Switching current AC1 (cos ϕ > 0.8): | 16 A |
Fluorescent lamps: | 16 AX |
Current carrying capacity | |
Neighbouring outputs: | Σ 20 A |
Device: | Σ 160 A |
Loads per output | |
Ohmic load: | 3000 W |
Capacitive load: | 16 A / 140 µF |
Motors: | 1380 VA |
Switch-on current 200 µs: | max. 800 A |
Switch-on current 20 ms: | max. 165 A |
Lamp loads | |
Incandescent lamps: | 3000 W |
HV halogen lamps: | 2500 W |
LV halogen lamps with | |
electronic transformers: | 1500 W |
inductive transformers: | 1200 VA |
Fluorescent lamps T5/T8 | |
non-compensated: | 1000 W |
parallel compensated: | 1160 W / 140 µF |
lead-lag circuit: | 2300 W / 140 µF |
Compact fluorescent lamps | |
non-compensated: | 1000 W |
parallel compensated: | 1160 W / 140 µF |
Mercury vapour lamps | |
non-compensated: | 1000 W |
parallel compensated: | 1160 W / 140 µF |
Connection, power supply and load | |
Connection mode: | screw terminals |
single wire: | 0.5 ... 4 mm² |
stranded without ferrule: | 0.5 ... 4 mm² |
stranded with ferrule: | 0.5 ... 2.5 mm² |
KNX | |
Rated voltage KNX: | DC 21 ... 32 V SELV |
Power consumption KNX: | typical 150 mW |
Connection, KNX: | terminal |
Approvals: | VDE |