Loading... Please wait...Currency Displayed in
Enables humidity control devices to be switched on according to needs.
- Monitoring and regulation of relative humidity by controlling fans, drying units and air humidifiers
- Temperature-compensated humidity sensor
- Variable relative humidity as setpoint based on printed scale in % rh
- Includes fixing bracket with seal for duct or wall mounting
- For fitting in a ventilation duct or on a wall
- With single-pole change-over contacts and fixed switching difference Xsd
- Immersion depth 130...156 mm; includes fixing bracket
| Power supply | |
| Max. load | 5(3) A, 250 V~ |
| Max. load | 100 mA, 24 V |
| Parameters | |
| Setting range | 15...95% rh |
| Setting accuracy | ±5% rh |
| Humidity calibration at | 55% rh, 23 °C |
| Temperature influence | Compensated |
| Long-term stability/td> | –1.5% rh/a |
| Time constant in moving air (0.2 m/s) | Approx. 3 min |
| Switching difference Xsd | 4% rh (after humidity calibration) |
| Max. air speed | 10 m/s |
| Type | Switching range Xsh | Number of switches | Weight |
| HBC111F001 | - | 1 | 0.33 kg |
| HBC112F001 | 6...25% rh | 2 | 0.33 kg |