Allows demand-controlled regulation of ventilation systems and reduces energy consumption.
- Measures the relative mixed gas concentration (organic components in the room air), such as tobacco smoke, kitchen vapours or human body odours
- Demand-based ventilation control in buildings such as restaurants and offices
- For measuring air quality in air ducts
- Automatic self-calibration through software algorithm
- Calibrated ex works and ready to use immediately
- The sensors have been developed according to the DIN EN 13779, DIN EN 15251, VDI 6038 and 6040 directives
- Mounting flange supplied
Power Supply | |
Power Supply | 15...24 V= (±10%) or 24 V~ (±10%) |
Power Consumption | Max. 1.5 W (24 V=) | 2.9 VA (24 V~) |
Peak inrush current | 10 A < 2 ms |
Output Signal | |
Output signal | 0...10 V Min. load: 10 kΩ |
Parameters | |
Flow speed | Min. 3 m/s Max. 10 m/s |
Readiness for operation | 2 minutes (operational), 15 minutes (max. precision) |
Time characteristic in moving air (3 m/s) | 5 minutes |
Measuring range | 0...100% |
Serviceable life | Typically 10 years |
Sensor | VOC sensor, heated tin dioxide semiconductor |
Type | Description |
EGQ110F031 | Duct transducer; VOC; 0-10 V |