Currency Displayed in
How energy efficiency is improved
Absolutely no losses through leaks. Energy is restrained.
- Regulation of heating zones, air secondary-treatment units and fan coil units in combination with AXT 211, AXS 215S or AXM 217(S)
- Flat-sealing standard version or version with clamping-ring screw fitting for pipe Ø 15 mm with DN 10
- Valve with male thread as per DIN EN ISO 228-1, class B
- Stuffing box can be replaced under system pressure
- Control passage AAB is closed when the spindle is moved in
- Closing procedure against the pressure
- Valve body made of nickel-plated cast brass for DN 10 and gun metal for DN 15 and DN 20
- Plug with EPDM soft seal
- Stainless-steel spindle
- Stuffing box with double O-ring seal
Type | Nominal Diameter | Kvs Value | Connection | Weight |
VUL010F340 | DN 10 | 0.16 m³/h | G½" B | 0.19 kg |
VUL010F330 | DN 10 | 0.4 m³/h | G½" B | 0.18 kg |
VUL010F320 | DN 10 | 0.63 m³/h | G½" B | 0.18 kg |
VUL010F310 | DN 10 | 1 m³/h | G½" B | 0.18 kg |
VUL010F300 | DN 10 | 1.6 m³/h | G½" B | 0.18 kg |
VUL015F310 | DN 15 | 2.5 m³/h | G¾" B | 0.28 kg |
VUL015F300 | DN 15 | 3.5 m³/h | G¾" B | 0.28 kg |
VUL020F300 | DN 20 | 4.5 m³/h | G1" B | 0.33 kg |
VUL010F630 | DN 10 | 0.4 m³/h | Clamping ring vers. Ø15 mm | 0.18 kg |
VUL010F620 | DN 10 | 0.63 m³/h | Clamping ring vers. Ø15 mm | 0.18 kg |
VUL010F300 | Small trough valve;DN10PN16;G1/2A;Kvs=1.6; DN 10 - 1 m³/h | SAUTER - Three-way flanged valvePN16,DN65,kvs63, 40mm |
VUL010F310 | Small trough valve;DN16PN16;G1/2A;Kvs=1.0; DN 10 - 1.6 m³/h | SAUTER - Three-way flanged valvePN16,DN65,kvs63, 40mm,Si |
VUL010F320 | Small trough valve;DN10PN16;G1/2A;Kvs=0.63; DN 10 - 0.63 m³/h | SAUTER - Three-way flanged valvePN25/16,DN80,kvs100, 40mm |
VUL010F330 | Small trough valve;DN10PN16;G1/2A;Kvs=0.40; DN 10 - 0.4 m³/h | SAUTER - Three-way flanged valvePN25/16,DN100,kvs160, 40mm |
VUL010F340 | Small trough valve;DN10PN16;G1/2A;Kvs=0.16; DN 10 - 0.16 m³/h | SAUTER - Three-way flanged valvePN25,DN125,kvs250, 40mm |
VUL010F600 | Small through valve;DN10PN16;D=15mm;Kvs=1.6;=% | SAUTER - Three-way flanged valvePN25,DN150,kvs340, 40mm |
VUL010F610 | Small through valve;DN10PN16;D=15mm;Kvs=1.0;=% | SAUTER - Small 3-way valve;DN10PN16;G1/2A;Kvs=1.6;=% |
VUL010F620 | Small through valve;DN10PN16;D=15mm;Kvs=0.63;=% | SAUTER - Small 3-way valve;DN10PN16;G1/2A;Kvs=1.0;=% |
VUL010F630 | Small through valve;DN10PN16;D=15mm;Kvs=0.40;=% | SAUTER - Small 3-way valve;DN10PN16;G1/2A;Kvs=0.63;=% |
VUL015F300 | Small through valve;DN15PN16;G3/4A;Kvs=3.5; DN 15 - 3.5 m³/h | SAUTER - Petite vanne 3voies;DN10PN16;G1/2A;Kvs=0.40;=% |
VUL015F310 | Small through valve;DN15PN16;G3/4A;Kvs=2.5; DN 15 - 2.5 m³/h | SAUTER - Small 3-way valve;DN10G1/2A;Kvs=1.6;=%;Bypass |
VUL020F300 | Small through valve;DN20PN16;G 1A;Kvs=4.5; DN 20 - 4.5 m³/h | SAUTER - Small 3-way valve;DN10G1/2A;Kvs=1.0;=%;Bypass |
Datasheet
Fitting Instructions: AXM217, AXM217S
Fitting Instructions: VUL, BUL