Currency Displayed in
How energy efficiency is improved
Precise cut-off with minimum leakage
- 2-way cut-off ball valve for use in closed circuits in heating, ventilation and air conditioning systems
- As a cut-off device and control unit for 2-point control in combination with valve actuators AKM 105(S), 115(S) and AKF 112, 113(S)
- Fast changeover in 6 s with valve actuator AKM115SF152
- Low torque due to collar mounted on O-ring
- Ball valve with male thread as per ISO 228-1 G..B
- Body made of dezincification-resistant cast brass
- Ball made of dezincification-resistant brass, chrome-plated and polished surface
- Strainer and screw fitting available as accessories
- Water quality as per VDI 2035
- French drinking water approval ACS
Parameters | |
Nominal pressure: | 40 bar |
Leakage rate: | Waterproof as per EN 60534-4 L/1, better than class 5 |
Angle of rotation: | 90° |
Ambient conditions | |
Operating temperature: | -10...130 °C, no condensation |
Operating pressure: | Liquids: 40 bar (-10...50 °C),35 bar (130 °C), Gases: 20 bar |
Type | Nominal diameter | Connection ISO 228-1 | Kvs value | Weight |
VKAA015F300 | DN 15 | G 1" B | 9 m3 | 0.36 kg |
VKAA020F300 | DN 20 | G 1¼" B | 17 m3 | 0.55 kg |
VKAA025F300 | DN 25 | G 1½" B | 22 m3 | 0.57 kg |
VKAA032F300 | DN 32 | G 2" B | 35 m3 | 0.84 kg |
VKAA040F300 | DN 40 | G 2¼" B | 68 m3 | 1.29 kg |
VKAA050F300 | DN 50 | G 2¾" B | 96 m3 | 1.98 kg |