Loading... Please wait...Currency Displayed in
- 4-way switching actuator MIX2
- Base module MIX2
- Can be upgraded to maximum of 12 channels
- Up to two extension modules MIX or MIX2 can be connected to one base module
- Device and KNX bus module can be swapped independently of each other
- Removable KNX bus module enables devices to be changed without reprogramming
- Manual set-up and use of switching actuators is possible without KNX bus module
- LED switching status display for each channel
- Manual operation on device (even without bus connection)
- Adjustable characteristics: e.g. switching, delayed switching, pulse function
| Operating voltage KNX | Bus voltage, ≤4 mA |
| Operating voltage | 110 - 240 V AC 50 - 60 Hz |
| Stand-by consumption | ~0.3 W |
| Installation type | DIN rail |
| Width | 4 modules |
| Type of connection | KNX bus terminal |
| Max. cable cross section | Solid wire: 0.5 mm² (Ø 0.8) to 4 mm² | Stranded wire with end sleeve: 0.5 mm² to 2.5 mm² |
| Number of channels | 4 |
| Type of contact | NO contact, 16 A, 3 A |
| Opening width | < 3 mm |
| Resistive load | 3680 W |
| Incandescent/halogen lamp load | 2000 W |
| Fluorescent lamp load (conventional) parallel-corrected | 1300 W (140 µF) |
| Fluorescent lamp load (conventional) not corrected | 2000 VA |
| Fluorescent lamp load (electronic ballast) | 1200 W |
| Energy saving lamps | 300 W |
| LED lamp < 2 W | 55 W |
| LED lamp 2-8 W | 600 W |
| LED lamp > 8 W | 600 W |
| Inrush current | max. 800 A / 200 µs |
| Voltage output | 240 V AC |
| Switching output | Potential-free |
| Switching of various phases | Possible |
| Suitable for SELV | Yes if all channels switch at SELV |
| C load | No |
| Type | Base module |
| Ambient temperature | -5°C ... 45°C |
| Type of protection | IP 20 |
| Protection class | II |