Rail mounting device, 4 rail units
with manual electronic operation and LED status indication
Only with the ETS 3.0d version or later versions the full functionality will be available.
ETS product family: Output
Product type: Binary output
- Switching of AC 110 ... 230 V electrical loads with floating contacts
- Switching of electrically-driven blinds, shutters, awnings and similar hangings
- Heating outputs: electronic outputs for switching electro-thermal valve drives
- Outputs can be operated manually, construction site mode
- Feedback in manual mode and in bus mode
- Scene function
- Disabling of individual outputs manually or by bus
- Operation as NO or NC contacts
- Logic operation and forcing function
- Feedback function
- Central switching function with collective feedback
- Time functions: switch-on delay, switch-off delay, staircase lighting timer with pre-warning function
- Suitable for 110 ... 230 V AC motors
- Blind/shutter position directly controllable
- Slat position directly controllable
- Feedback of movement status, blind/shutter position and slat position
- Forced position through higher-level controller
- Safety function: 3 independent wind alarms, rain alarm, frost alarm
- Sun protection function
- Switching operation or PWM operation
- Actuators with characteristics opened or closed without power controllable
- Overload-protected, short circuit-protected
- Emergency operation in case of bus voltage failure for summer and winter
- Protection against jamming valves
- Forced position
- Cyclical monitoring of the input signals can be parameterised
| KNX supply: | DC 21 ... 32 V SELV |
| Power consumption KNX: | max. 150 mW |
| Power supply mains: | AC 110 ... 230 V ~, 50/60 Hz |
| Power loss: | max. 6 W |
| Ambient temperature: | -5 ... +45 °C |
| Storing temperature: | -25 ... +70 °C |
| Mounting width: | 72 mm (4 rail units) |
| Connection, KNX: | terminal |
| Connection, mains and outputs: | |
| Connection mode: | screw terminals |
| single wire: | 0.5 ... 4 mm² |
| stranded without ferrule: | 0.5 ... 4 mm² |
| stranded with ferrule: | 0.5 ... 2.5 mm² |
| Heating outputs | |
| Number: | 2 |
| Contact type: | semiconductor, ε |
| Switching voltage: | AC 230/240 V ~ |
| Switching current: | 5 ... 50 mA |
| Number of drives per output: | max. 4 |
| Relay outputs | |
| Number: | 4 (2 channels for operating blinds) |
| Contact type: | floating NO contact (µ contact) |
| Switching voltage: | AC 230/240 V ~ |
| Breaking capacity AC1: | 16 A |
| Breaking capacity AC3: | 6 A |
| Breaking capacity fluorescent lamps: | 16 AX |
| Switching capacities per output | |
| Ohmic load: | 3000 W |
| Capacitive load: | 16 A / max. 140 µF |
| Motors: | 1380 VA |
| Lamp loads | |
| Incandescent lamps: | 3000 W |
| HV halogen lamps: | 2500 W |
| LV halogen lamps with | |
| electronic transformers: | 1500 W |
| inductive transformers: | 1200 VA |
| Fluorescent lamps: | |
| non-compensated: | 1000 W |
| parallel compensated: | 1160 W / max. 140 µF |
| lead-lag circuit: | 2300 W / max. 140 µF |
| Approvals: | VDE |