Currency Displayed in
The Lingg & Janke KNX DIN rail meters are multifunctional three phase energy meters of only 90 mm (5 Units) width offering exceptional flexibility and accuracy. Providing direct connection, these meters are capable of analyzing and monitoring a variety of parameters and can be employed in even the most demanding residential, commercial or industrial field of application. They combine the functions of a multimeter, energy meter and data logger in a single device. Using KNX FacilityWeb, the meters can read out and log numerous measured values, such as active and reactive energy, active and reactive power, voltage, current and power factor. Each one of the different output values can be monitored with two thresholds.
The integrated KNX/EIB module stores the measured data every 15 minutes over a period of one year and provides full FacilityWeb capability. Every meter has its own home page. The meter readings can be read out directly via a network coupler using a standard Internet browser, or transmitted for further processing and billing purposes using FTP. Consistent communication based on the TCP/IP and KNX protocol is the key to fast and costeffective acquisition of operating and energy consumption data.
- the Standard KNX meter can be used for accumulating unidirectional 3-phase meter for active energy, active power, voltage, current and power factor, 4 tariffs, one direction, max. 75A
- the Superior KNX meter: accumulating bidirectional 3-phase meter for active and reactive energy, active and reactive power, voltage, current and power factor, 4 tariffs, two directions, max. 75A, in addition 4 switching outputs
- integrated KNX BCU with FacilityWeb
- adds quick-ability
Max. Group Addresses: | 108 |
Voltage: | 3 x 230V / 400V AC 0.25-5(75)A |
Frequency: | 50 - 60 Hz |
Starting Current: | <9mA |
Dimension WxHxD(mm): | 90 x 91 x 68 (5 units) |
Installation: | for mounting on DIN rail, TH35 |
Operating Temperature: | 5 .... +45 °C |
Consumption: | |
Optical Interface: | EN62056-21 |
Lower Terminals: | 0.5 bis 35mm², 2 Nm |
Upper Terminals: | bis 2.5mm², 0,4 Nm |
Accuracy Class: | B (+/-1%) for active Energy EN 50470-1,-3 |
Switching Outputs: | Opto Power MOSFET 230V AC / DC, max. 90 mA |