Loading... Please wait...Currency Displayed in
with integrated BCU
ETS product family: Physical sensors
Product type: Brightness
- Measurement and control of lighting indoors or in protected outdoor area
- Clamp mounting in suspended ceilings
- Ceiling installation on fixed ceilings in appliance box according to DIN 49073 with flush mounting set (ref.-no.: PMM-UP-SET-WW)
- Surface-mounted ceiling installation with surface mounting set (ref.-no.: PMM-AP-SET-WW)
- Asymmetrical measuring surface
- Integrated bus coupling unit
- Integrated brightness sensor
- Brightness sensor function with 3 limiting values
- Brightness limiting values (3 channels) with output functions switching, value transmitter and scene extension
- Light control with max. 3 channels, setpoint shift in operation, separate configuration of dimming-up, control and dimming-down phase
- On-off control possible for switch actuators
- Power supply via bus voltage
| Rated voltage KNX: | DC 21 ... 32 V SELV |
| Current consumption KNX: | max. 10 mA |
| Connection bus: | terminal |
| Protection class: | III |
| Ambient temperature: | -25 ... +55 °C |
| Storage/transport temperature: | -25 ... +70 °C |
| Relative humidity: | 10 ... 100 % (no condensation) |
| Protection level: | IP 44 |
| Ceiling cut-out (Ø x D): | 44 x 35 mm |
| Dimensions (Ø x H): | 53.5 x 38 mm (with design ring) |
| Max. thickness of the suspended ceiling: | approx. 25 mm |
| Installation depth: | min. 35 mm |
| Distance between concrete ceiling and suspended ceiling: | min. 20 mm |
| Design ring Ø inside: | 35.6 mm |
| Design ring Ø outside: | 53.5 mm |
| Profile height design ring: | 1.8 mm |
| Profile height lens: | 5.5 mm |
| Brightness sensor | |
| Measuring range: | 10 ... 2.000 lx |
| Accuracy (? 80 lx): | ± 10 lx |
| Accuracy (> 80 lx): | ± 5 % |