Currency Displayed in
1-gang switch actuator with two inputs for installation in a size 60 switch box or ceiling socket-outlet with hook. Floating contacts can be connected to the two inputs. The first input is assigned to the actuator at the factory, enabling operation without programming.
Connection to 230 V via a flexible cable, approx. 20 cm long. The inputs and the KNX are connected via a 6-core, approx. 30 cm long, connecting cable. The connecting cable for the inputs can be extended to a max. of 5 m.
Switch actuator functions:
- Operation as break contact or make contact
- Selection of default position on bus voltage failure/recovery
- Switch on and/or off delay
- Time switch function
- Switching
- Status feedback
- Logic operation
- Disable function or priority control
- Status feedback object can be inverted
Binary input function:
- Free assignment of the switching, dimming, blind and valuator functions
- Locking object
- Behaviour when bus voltage recovers
Switching:
+ Two switch objects per input
+ Dimming: Single surface and dual-surface operation
+ Time between dimming and switching and dim step values
+ Telegram repetition and send stop telegram
Blinds:
+ Command on rising edge (none, UP, DOWN, TOGGLE)
+ Operation concept (Step - Move - Step or Move - Step)
+ Time between short and long operation
+ Slat adjustment time
- Valuator and lightscene ext. input: Edge (push-button as make contact, push-button as break contact, switch) and value on edge
- Value adjustment via long push-button action for valuator
- Lightscene ext. unit with memory function.
Device mounting: | Flush |
[Ue] Rated operational voltage: | 230 V |
Network frequency: | 50/60 Hz |
[In] Rated current: | 16 A |
Load type: | Low voltage halogen lamp with wire-wound transformer : <= 1000 VA Incandescent lamps : <= 2500 W, 230 V AC Halogen lamps : <= 2200 W, 230 V AC Low voltage halogen lamp with electronic transformer : <= 1000 W Capacitive : 10 A - 105 µF, 230 V AC |
IP degree of protection: | IP20 |