Currency Displayed in
Rated voltage 24 V DC
range 0 ... 60 000 lux, linear
The brightness sensor is used for the measuring and evaluation of the brightness.
The dawn sensor is used for the measuring and evaluation of the brightness (dawn/dusk).
The temperature sensor is used for the measuring and evaluation of the temperature.
The value measured by the sensor is transmitted to an analogue output signal of 0 ... 10 V by the electronics.
Connections:
Plastic housing with PG7 thread + screw and pressure / moisture compensation (recommended cable 3 x 0.25 mm2)
+UB: operating voltage 24 V DC
GND: corresponding ground
OUT: output 0 ... 10 V
Supply voltage: | 24 V DC (15 ... 30 V DC) |
Connection: | screw terminals |
Terminals for: | 2.5 mm² |
Connection cable: | through screwed conduit entry PG 7 |
Recommended cable: | 3 x 0,25 mm² |
Cable length: | max. 100 m |
Output: | 0 ... 10 V DC (into a load of at least 1 kΩ, short-circuit protected) |
Ambient temperature: | -30 ... +70 °C |
Protection level: | IP 65 |
Mounting position: | optional |