Currency Displayed in
How energy efficiency is improved
Overload protection and end stop detection for efficient usage of energy
- For operating air dampers, shut-off dampers, butterfly valves and multi-leaf dampers
- For controllers with switching (2- and 3-point) output
- Self-centring spindle adapter
- Manual adjustment using hexagon socket, including locking of gear unit
- Maintenance-free
- Suitable for all fitting positions
Power Supply | |
Power supply 230 V~: | ±10%, 50...60 Hz |
Power supply 24 V~: | ±20%, 50...60 Hz |
Power supply 24...48 V=: | ±20% |
Parameters | |
Torque and holding torque: | 7 Nm |
Angle of rotation: | Max. 95° |
Admissible damper surface area: | Approx. 1.5 m² |
Running time for 90° motor: | 90 s |
Running time for 90° spring: | 15 s |
Ambient Conditions | |
Admissible ambient temperature: | –32...55 °C |
Admissible ambient humidity: | 5...95% rh, no condensation |
Construction | |
Housing: | Cast aluminium |
Power cable: | 0.9 m, 0.75 mm² |
Type | Control Function | Voltage | Power consumption | Weight |
ASF112F120 | 2-point | 230 V~ | 4.5 W, 7.0 VA | 1.2 kg |
ASF112F122 | 2-point | 24 V~/24...48 V= | 3.5 W, 5.0 VA | 1.2 kg |
ASF112F220 | 2-point | 230 V~ | 4.5 W, 7.0 VA | 1.3 kg |
ASF112F222 | 2-point | 24 V~/24...48 V= | 3.5 W, 5.0 VA | 1.3 kg |
ASF113F122 | 3-point | 24 V~/24...48 V= | 3.5 W, 5.0 VA | 1.2 kg |
ASF112F220, ASF112F222: Double auxiliary contacts 6(2) A; 24...250 V~ with cable 0.9 m; 6 × 0.75 mm² |