Currency Displayed in
How energy efficiency is improved
Electric cut-off in end position to save energy
- Actuation of control units such as air dampers, gates, butterfly valves, etc. for controllers with a switching output (3-point)
- Synchronous motor with limit switch
- Maintenance-free gear unit
- Positions the control unit to any intermediate position
- Cable gland M20 × 1.5
- Crank for manual adjustment
Power Supply | |
Power supply 230 V~ | ±15%, 50...60 Hz |
Power supply 24 V~ | ±20%, 50...60 Hz |
Parameters | |
Angle of rotation | 90° |
Ambient Conditions | |
Admissible Ambient Temperature | –20...60 °C |
Admissible Ambient Humidity | 5...95% rh |
Storage and Transport Temperature | -30...70 °C |
Type | A44W0F001 | A44W0F020 | A44W1F001 | A44W1F020 | A44W2F001 | A44W2F020 |
Torque (Nm) | 25 | 25 | 30 | 30 | 30 | 30 |
Holding torque (Nm) | 22 | 22 | 30 | 30 | 30 | 30 |
Running time for 90° (s) | 30 | 30 | 60 | 60 | 120 | 120 |
Admissible damper surface area (m²) | 8 | 8 | 10 | 10 | 10 | 10 |
Power con- sumption with 60 Hz | 10.4 W | 10.4 W | 10.4 W | 10.4 W | 4.8 W | 4.8 W |
Leistungsauf- nahme_bei 50Hz_M | 9.2 W | 9.2 W | 9.2 W | 9.2 W | 3.8 W | 3.8 W |
Voltage | 230 V~ | 24 V~ | 230 V~ | 24 V~ | 230 V~ | 24 V~ |
Weight (kg) | 2.5 | 2.5 | 2.5 | 2.5 | 2.2 | 2.2 |