Currency Displayed in
The weather station records and processes analogue sensor signals such as wind speed, brightness, twilight, precipitation and a DCF-77 signal. Up to four analogue sensors and the DCF-77 weather combi-sensor can be connected in any combination. In connection with the 4-gang analogue input module, 8 analogue inputs are available, to which the connection is made using the sub-bus.
For installation on DIN rails EN 50022.
The bus is connected using a bus connecting terminal; a data rail is not necessary. If DCF-77 weather combi-sensors are used, it is possible to access a pre-configured setting in the software. The measured values are converted by the weather station into 1 byte / 2 byte telegrams (EIS 6/5 value). This enables bus devices (visualisation software, measured value displays) to access the control processes, generate signals or control weather-dependent processes. Programming is performed using the ETS tool for the weather station.
- Two limit values per sensor (not for rain)
- Connection of multiple wind sensors
- 14 signals can be evaluated
- Evaluation of DCF-77 time signal (date and time)
- Astro function
- Logic operation controller for application of limit-value-dependent actions (even external)
- Shading of individual façade segments
- Signal monitoring of the combi-sensors with object for the following protective measures
- Checking the wind signal for conclusiveness with object for the following protective measures
- Selective façade shading (for 4 façades) with adjustment of the basic brightness, façade alignment, angle of opening relative to the sun.
- External objects for intervention in basic brightness, angle of opening and limit values
- Alarm byte
- Continuity monitoring with report on the bus
Auxiliary voltage: | AC 24 V (+/-10 %) |
Analogue inputs: | 4 |
Current interface: | 0 ... 20 mA, 4 ... 20 mA |
Voltage interface: | 0 ... 1 V, 0 ... 10 V |
Outputs: | DC 24 V, 100 mA |
Device width: | 4 modules = approx. 72 mm |