- 2 binary inputs
- ETS product family: Illumination
- Product type: Dimmer
- Switching and dimming of incandescent lamps, 230 V halogen lamps and LV halogen lamps with inductive transformers or electronic transformers
- Installation in appliance box to DIN 49073
- Automatic selection of the dimming principle suitable for the load
- Protected against no-load, short-circuit and overheating
- Feedback of the switching position and the dimming value
- Parameterisable switch-on and dimming behaviour
- Timed dimmer: switch-on delay, switch-off delay, staircase lighting timer
- Light scene operation
- Two binary inputs for potential-free contacts, usable as extension inputs for local operation
- Supply via bus, no additional power supply necessary
- Mains failure longer than approx.0.7 seconds leads to switch-off of the dimmer actuator
Output: | 1 Power MOS-FET |
Dimming method: | trailing edge or leading edge phase control |
Terminals | |
Output cable: | L = black, dimming output = brown, 0.75 mm² length approx. 20 cm |
Bus and control cable: | KNX + red KNX black binary input 1 green GND white binary input 2 yellow GND brown length approx. 33 cm, extendible to 5 m max. |
Satellite input: | depending on parameterisation either as extension inputs for push-button local control of the actuator or as independent binary inputs acting on the bus |
Dimensions (Ø x H): | 63 x 25 mm |
Rated voltage: | AC 230 V ~, 50/60 Hz |
Rated current: | 0.9 A |
Minimum load: | 50 W |
Power loss: | 2 W |
Connected load | |
Total connected load: | 210 W/VA |
Ohmic load: | 50 ... 210 W |
Incandescent lamps: | 50 ... 210 W |
HV halogen lamps: | 50 ... 210 W |
LV halogen lamps with | |
inductive transformers: | 50 ... 210 VA |
electronic transformers: | 50 ... 210 VA |
Mix of the specified load types (do not mix capacitive loads with inductive loads). | |
When using mixed loads with inductive transformers, the ohmic load must not exceed 50 %. | |
Approvals: | VDE |